About the PZK-560K
The PZK-560K is situated in the substation controls the opening and closing of the switch onto the line and monitoring the status of the bus switch. It comprises a PZK-56K (B / C or A) monitoring and control unit.
Key features
- Monitoring and control, including the identification of distribution line fault (including low current earth faults) their location, isolation and restoration of supply to unfaulted sections. It does not rely on a distribution network automation master (substation) control, as it can make decisions based on dynamic, distributed current differential protection, distributed remote tripping anti-islanding protection, distributed planning Island power supply imbalance
- Optional distribution transformer and reactive power compensation capacitor measurement and control functions.
- It can be flexibly configured to realise remote signalling, remote measurements and remotecontrol functionality.
- The use of voltage transformers or distribution transformers or dedicated power output as a power inputs, dual power automatically switches.
- Back-up power can be configured as needed to meet the requirements of AC power loss operation.
- Backup power optional maintenance-free lead-acid batteries, super capacitors or lithium batteries.
- Can be configured to use local and remote-control switches.
- With centralised and distributed installation.
- The distributed method allows several PZK-56A monitoring and control units to be installed in separate cubicles in the substation. One unit acts as the principal which communicates with a remote master station. It also communicates with the other units through a CAN bus network.
Technical Characteristics
- High-performance digital signal processor, large-scale field programmable logic array, with powerful real-time data processing
- Powerful memory resources to meet the needs of advanced application software and communications, system management, HMI and other functions
- Based on real-time Linux operating system, a hierarchical, modular software architecture, applications accessible through an open interface Ready-to-use, providing a unified support platform for a variety of smart distribution network applications.
- Provides a PC-like software development environment, allowing new applications to be easily opened and new application features to be added. Designed with hardware and software redundancy, with a strong fault tolerance and selfdiagnosis with a self-recovery capability.
- Communication based on the IEC 61850 standard design, with self-discovery, selfdescription function, realisation and distribution master plug and play.
- Easy to use HMI, with monitoring of operating conditions, site commissioning and easy maintenance.
- WEB service capabilities, allowing the use of a common web browser, access to real-time data, downloaded historical data and configuration files
Technical Data
| POWER PARAMETERS | ||
|---|---|---|
| Power supply | 60/110/220 Vac or 48/110/220 Vdc | Dual power with automatic switching |
| Backup power | Different options available / configure as required | Maintenance-free lead-acid batteries, lithium batteries or supercapacitors |
| INPUTS AND OUTPUT | ||
| Signal inputs | 9 – 84 | In groups of three, that can access the voltage or current transformers or sensors, zero sequence voltage and current can be directly accessed or derived from internal three-phase synthesis |
| DC inputs | 2-4 | ± 10VDC, ± 30VDC or 4-20mA |
| Switch inputs | 24 – 129 | 24/48VDC adaptive, configurable two-point remote communication |
| Switch output | 6– 24 | Optically isolated outputs |
| Control output | 4 - 24 SBO* | 1 SBO* includes a sub-gate control, and a closing control |
| COMMUNICATION PARAMETERS | ||
| Communication interface | 3 Ethernet communication ports, 5 RS-232/485 communication ports, 1 CAN field bus interface, 1 Ethernet maintenance communication port | |
| Communication protocol | IEC 60870-5-104 / 101, DNP3.0, SC1801, MODBUS | |
| PHYSICAL PARAMETERS | ||
| Dimensions | 400mm × 480mm × 140mm (height × width × depth), wall-mounted structure 150mm × 300mm × 240mm (height × width × depth), embedded structure Customised packages can be created if required | |
| Installation method | wall fixed cabinet, vertical or horizontal orientation or embedded | |
*SBO – Select before operate