About the PZK-560Z
Based on the PZK-56A device, the PZK-560Z column-mounted switch terminal device is designed for distribution overhead line switch monitoring and control. It features flexible power supply based on the line voltage optionally backed-up with maintenance-free leadacid batteries, super capacitors or lithium batteries
Key features
- Communication with the main substation to monitor and control the overhead line switch status
- Fault location, isolation and supply restoration (FLISR), including low-current earth faults
- Local automation without relying on the distribution network automation master (substation) control
- Distributed protection for overcurrent, current differential and remote trip anti-islanding
- Islanding unbalanced power control and distributed low-current earth fault location and tripping
- Flexible configuration to support 'two remote' or 'three remote' functionality
Technical Data
| POWER PARAMETERS | ||
|---|---|---|
| Power supply | 60/110/220Vac | Dual power automatically switched |
| Backup power | Different options available/ Configure as required | Maintenance-free lead-acid batteries, lithium batteries or supercapacitors |
| INPUTS AND OUTPUT | ||
| Signal inputs | 9 | A group of three, access to voltage, current transformers or sensors, zero sequence voltage / current can be directly accessed or internal three-phase synthesis |
| DC inputs | 2 | ± 10VDC, ± 30VDC or 4 - 20mA |
| Switch inputs | 24 | 24 / 48VDC adaptive, configurable two-point remote communication |
| Switch output | 6 | Opto-isolated |
| Control Output | 4 SBO* | 1 SBO* includes a sub-gate closing control |
| COMMUNICATION PARAMETERS | ||
| Communication Interface | 3 Ethernet communication ports, 5 RS-232/485 communication ports, 1 CAN field bus interface, 1 Ethernet maintenance communication port | |
| Communication Protocol | IEC 60870-5-104 / 101, DNP3.0, SC1801, MODBUS | |
| PHYSICAL PARAMETERS | ||
| Dimensions | 600mm × 450mm × 300mm (height × width × depth) | |
| Installation method | Pole mounted or tower suspension | |
*SBO – Select before operate